K-13 Product Specifications

Section 07218 K-13 Spray-On Systems Specification Guide 1003

Download K-13 specifications in pdf format

Download K-13 specifications in word format

PART 1 - GENERAL

1.01 Work Included: (Edit acoustical where required)

Sprayed cellulose thermal [and acoustical] insulation..

1.02 Related Items:

  • Clips, hangers, supports, sleeves and other attachments to spray bases are to be placed by other trades prior to the application of sprayed insulation.
  • Ducts, piping, conduit or other suspended equipment shall not be positioned until after the application of sprayed insulation.
  • Roof penetrations to be installed prior to application.

1.03 Quality Assurance:

  • Manufacturer must be ISO 9001:2000 Certified.
  • Applicator: Licensed by manufacturer.
  • Manufacturer must subscribe to independent laboratory follow-up inspection services of Underwriters Laboratories and Factory Mutual. Each bag shall be labeled accordingly.
  • Mock up: Apply a 100 square foot representative sample to be reviewed by the Architect and/or Owner prior to proceeding.

1.04 Submittals:

  • Submit product data and manufacturer's certificate that the product meets or exceeds specified requirements.
  • Manufacturer's written certification that product contains no asbestos, fiberglass or other man made mineral fibers.
  • Copy of manufacturer's ISO 9001:2000 Certification.

1.05 Product Delivery, Storage and Handling:

  • Deliver in original, unopened containers bearing name of manufacturer, product identification and reference to U.L. testing.
  • Store materials dry, off ground, and under cover.
  • Protect liquid adhesive from freezing.

PART 2 - PRODUCTS

2.01 Acceptable Manufacturers:

  • International Cellulose Corporation
    12315 Robin Boulevard
    Houston, Texas 77045
    (713) 433-6701 or (800) 444-1252
    FAX: (713) 433-2029

  • For approved applicators contact ICC at 800-444-1252.

2.02 Materials:

  • K-13 Spray-On-Systems.
  1. Color shall be as indicated in Schedule 3.05.[Color selection will affect price]
  2. Apply at minimum thickness to provide an R-value(s) as indicated in Schedule 3.05. [Add Thermal Resistance values if applicable]
  3. Comply with ASTM E-736 for field-tested bond strength; tested @ > 5 years.
    • Not less than 400 psf
    • Not less than 600 times its weight @ 1"
  4. Comply with ASTM E-84/U.L. 723, Tested at a minimum of 5" thickness Class 1, Class A, Flame Spread 5, Smoke Development 5
  5. Comply with local Building Code requirements.
  6. Comply with ASTM E-1042.
  7. NRC Rating [Edit NRC rating if applicable]: Install at a minimum thickness to achieve a NRC rating as indicated in the Schedule 3.03

  8. Inches 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ NRC
    K-13 Sprayed Thermal and Acoustical Insulation ASTM C-423 on Solid Backing*
    1.00" .08 .29 .75 .98 .93 .96 .75
    1.00** .47 .90 1.10 1.03 1.05 1.03 1.00
    2.00" .26 .68 1.05 1.10 1.03 .98 .95
    3.00 .57 .99 1.04 1.03 1.00 1.00 1.00

    Some values interpolated **On lath

    Inches 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ NRC
    K-13 Sprayed Thermal and Acoustical Insulation Applied at 1.5" Ribbed Metal Deck*
    1.5 .36 .89 1.26 1.07 1.01 1.00 1.05
    3.00" .97 1.04 1.13 .99 .95 .98 1.05

    Some values interpolated **On lath

  9. Non corrosive per ASTM C 739.
  10. Bond Deflection per ASTM E-759: 6" Deflection in 10' Span - No Spalling or Delamination
  11. Cohesive Strength at time of application per Method WS-2000: > 700 Grams

PART 3 - EXECUTION

3.01 Examination

  • Examine surfaces and report unsatisfactory conditions in writing. Do not proceed until unsatisfactory conditions are corrected.
  • Verify surfaces to receive spray insulation to determine if priming/sealing is required to insure bonding and/or to prevent discoloration caused by migratory stains.

3.02 Preparation

  • Provide masking, drop cloths or other satisfactory coverings for materials/surfaces that are not to receive insulation to protect from over-spray.
  • Coordinate installation of the sprayed cellulose fiber with work of other trades.
  • Prime surfaces as required by manufacturer's instructions or as determined by examination.

3.03 Installation

  • Thickness will be determined as the minimum thickness measured as per ASTM E-605 field test procedure.
  • Install spray applied insulation according to manufacturer’s recommendations.
  • Cure insulation with continuous natural or mechanical ventilation.
  • Remove and dispose of over-spray.

3.04 Protection

  • Protect finished installation under provision of Division 1

3.05 Schedule

Provide a schedule when insulation requires listing by color, insulation value, NRC values and attributes.

END OF SECTION