K-13 Product Specifications
Section 07218 K-13 Spray-On Systems Specification Guide 1003
Download K-13 specifications in pdf format
Download K-13 specifications in word format
PART 1 - GENERAL
1.01 Work Included: (Edit acoustical where required)
Sprayed cellulose thermal [and acoustical] insulation..
1.02 Related Items:
- Clips, hangers, supports, sleeves and other attachments to spray bases are to be placed by other trades prior to the application of sprayed insulation.
- Ducts, piping, conduit or other suspended equipment shall not be positioned until after the application of sprayed insulation.
- Roof penetrations to be installed prior to application.
1.03 Quality Assurance:
- Manufacturer must be ISO 9001:2000 Certified.
- Applicator: Licensed by manufacturer.
- Manufacturer must subscribe to independent laboratory follow-up inspection services of Underwriters Laboratories and Factory Mutual. Each bag shall be labeled accordingly.
- Mock up: Apply a 100 square foot representative sample to be reviewed by the Architect and/or Owner prior to proceeding.
1.04 Submittals:
- Submit product data and manufacturer's certificate that the product meets or exceeds specified requirements.
- Manufacturer's written certification that product contains no asbestos, fiberglass or other man made mineral fibers.
- Copy of manufacturer's ISO 9001:2000 Certification.
1.05 Product Delivery, Storage and Handling:
- Deliver in original, unopened containers bearing name of manufacturer, product identification and reference to U.L. testing.
- Store materials dry, off ground, and under cover.
- Protect liquid adhesive from freezing.
PART 2 - PRODUCTS
2.01 Acceptable Manufacturers:
- International Cellulose Corporation
12315 Robin Boulevard
Houston, Texas 77045
(713) 433-6701 or (800) 444-1252
FAX: (713) 433-2029 - For approved applicators contact ICC at 800-444-1252.
2.02 Materials:
- K-13 Spray-On-Systems.
- Color shall be as indicated in Schedule 3.05.[Color selection will affect price]
- Apply at minimum thickness to provide an R-value(s) as indicated in Schedule 3.05. [Add Thermal Resistance values if applicable]
- Comply with ASTM E-736 for field-tested bond strength; tested @ > 5 years.
- Not less than 400 psf
- Not less than 600 times its weight @ 1"
- Comply with ASTM E-84/U.L. 723, Tested at a minimum of 5" thickness Class 1, Class A, Flame Spread 5, Smoke Development 5
- Comply with local Building Code requirements.
- Comply with ASTM E-1042.
- NRC Rating [Edit NRC rating if applicable]: Install at a minimum thickness to achieve a NRC rating as indicated in the Schedule 3.03
- Non corrosive per ASTM C 739.
- Bond Deflection per ASTM E-759: 6" Deflection in 10' Span - No Spalling or Delamination
- Cohesive Strength at time of application per Method WS-2000: > 700 Grams
| Inches | 125HZ | 250HZ | 500HZ | 1000HZ | 2000HZ | 4000HZ | NRC |
| K-13 Sprayed Thermal and Acoustical Insulation ASTM C-423 on Solid Backing* | |||||||
| 1.00" | .08 | .29 | .75 | .98 | .93 | .96 | .75 |
| 1.00** | .47 | .90 | 1.10 | 1.03 | 1.05 | 1.03 | 1.00 |
| 2.00" | .26 | .68 | 1.05 | 1.10 | 1.03 | .98 | .95 |
| 3.00 | .57 | .99 | 1.04 | 1.03 | 1.00 | 1.00 | 1.00 |
Some values interpolated **On lath
| Inches | 125HZ | 250HZ | 500HZ | 1000HZ | 2000HZ | 4000HZ | NRC |
| K-13 Sprayed Thermal and Acoustical Insulation Applied at 1.5" Ribbed Metal Deck* | |||||||
| 1.5 | .36 | .89 | 1.26 | 1.07 | 1.01 | 1.00 | 1.05 |
| 3.00" | .97 | 1.04 | 1.13 | .99 | .95 | .98 | 1.05 |
Some values interpolated **On lath
PART 3 - EXECUTION
3.01 Examination
- Examine surfaces and report unsatisfactory conditions in writing. Do not proceed until unsatisfactory conditions are corrected.
- Verify surfaces to receive spray insulation to determine if priming/sealing is required to insure bonding and/or to prevent discoloration caused by migratory stains.
3.02 Preparation
- Provide masking, drop cloths or other satisfactory coverings for materials/surfaces that are not to receive insulation to protect from over-spray.
- Coordinate installation of the sprayed cellulose fiber with work of other trades.
- Prime surfaces as required by manufacturer's instructions or as determined by examination.
3.03 Installation
- Thickness will be determined as the minimum thickness measured as per ASTM E-605 field test procedure.
- Install spray applied insulation according to manufacturer’s recommendations.
- Cure insulation with continuous natural or mechanical ventilation.
- Remove and dispose of over-spray.
3.04 Protection
- Protect finished installation under provision of Division 1
3.05 Schedule
Provide a schedule when insulation requires listing by color, insulation value, NRC values and attributes.
END OF SECTION